CPSC, Notifier Announce Recall for Fire Alarm Panels
Source: CPSC Recall #04508
Recall Date
2003-10-30
Manufacturer
Notifier, of Northford, Conn.
Units Affected
6,000
Products Involved
Fire Alarm Control Panel
Hazard
The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.
Remedy
Notifier will provide an upgraded CPU firmware set for each AM2020 and AFP1010 panel, at no charge.
Reported Injuries
Notifier has received eight reports of trouble signals alarming. In each case the problem was identified and corrected. No injuries have been reported.
Sold At
Notifier distributors nationwide, from January 2000 through May 2002. The list price for the CPU and DIA combination for the model AM2020 is about $6,400, and the list price for the CPU and DIA combination for the model AFP1010 is about $3,370.
Manufactured In
United States
Full Recall Description
The fire alarm control panel includes the central processing unit (CPU-2020 and CPU-2) and Display Interface Assembly (DIA-2020 and DIA-2) components of Notifier model AM2020 and AFP1010 fire alarm control panels with date codes from 0100 to 2003 and firmware version 3.0 and 3.01. The date codes appear on the back outer edge of the PC boards.
Data source: U.S. Consumer Product Safety Commission (CPSC) via SaferProducts.gov.
For the most current recall information, check directly with CPSC or the manufacturer.
Last verified: 2026-03-28