CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers

Recall Date
2002-10-02
Manufacturer
Invensys Building Systems, of Love Park, Ill.
Units Affected
Up to 560,000

Products Involved

Siebe actuators

Hazard

A spring mechanism integrated with the damper is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Remedy

To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Only actuators that fail testing will be replaced.

Reported Injuries

Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing.

Manufactured In

United States

Full Recall Description

These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947. See the associated recall alert for more details on the dampers and companies involved.